Follow the order. Stop at the first step that fails.
No 120V at the board: furnace switch, door switch, breaker (reset once). 120V but no 24V R to C: transformer or fuse. No W: thermostat or wire.
24V across a switch = that one is open. Hot limit: filter, blower, registers. Rollout tripped: furnace OFF CALL JOSH
120V, not running: motor CALL JOSH No 120V: board or an open safety. Weak or failed motor? Check the vent for a partial block.
WC low: blocked vent, intake, hose or trap. WC good but switch open: bad switch CALL JOSH Never jumper it.
120V, no glow: igniter (power off, wires off: OL = broken). No 120V: board. Don't touch the element.
24V, no flame: valve or no gas CALL JOSH No 24V: the board isn't calling for gas. Never touch the regulator or gas pipe.
Drops in 3 to 5 seconds: clean the rod, check the ground. Yellow, lazy or moving flame: OFF CALL JOSH
120V, no run: motor or capacitor. No 120V: board, relay or door switch. ECM motor: no ohm tests CALL JOSH
Burners cycle with the call on: filter, airflow, limit. Flame after the call ends: gas OFF, furnace out of service CALL JOSH