NO-HEAT TRUCK CARD · gas furnace

Follow the order. Stop at the first step that fails.

45 MIN, STILL STUCK?CALL JOSH 720-404-6680
STOP: gas smell, CO alarm or burnt wires. Everyone out. 911 and Xcel gas 800-895-2999 from outside, then CALL JOSH.
Power ON = volts · Power OFF = ohms · Check every reading twice · Never jumper a safety
1
Call for heat24V, W to C at the board
NO →

No 120V at the board: furnace switch, door switch, breaker (reset once). 120V but no 24V R to C: transformer or fuse. No W: thermostat or wire.

▼ YES
2
Board checks the safetiesBlink code. Limits and rollouts closed
NO →

24V across a switch = that one is open. Hot limit: filter, blower, registers. Rollout tripped: furnace OFF CALL JOSH

▼ YES
3
Inducer starts120V at the inducer motor
NO →

120V, not running: motor CALL JOSH No 120V: board or an open safety. Weak or failed motor? Check the vent for a partial block.

▼ YES
4
Pressure switch closes0V across it. WC on the manometer
NO →

WC low: blocked vent, intake, hose or trap. WC good but switch open: bad switch CALL JOSH Never jumper it.

▼ YES
5
Igniter glows orange120V at the igniter
NO →

120V, no glow: igniter (power off, wires off: OL = broken). No 120V: board. Don't touch the element.

▼ YES
6
Gas valve opens24V at MV and C. Meter on before the call
NO →

24V, no flame: valve or no gas CALL JOSH No 24V: the board isn't calling for gas. Never touch the regulator or gas pipe.

▼ YES
7
Flame lights and staysµA on the sensor wire
NO →

Drops in 3 to 5 seconds: clean the rod, check the ground. Yellow, lazy or moving flame: OFF CALL JOSH

▼ YES
8
Blower starts120V at the blower after the delay
NO →

120V, no run: motor or capacitor. No 120V: board, relay or door switch. ECM motor: no ohm tests CALL JOSH

▼ YES
9
Call ends cleanValve closes. Blower runs on, then stops
NO →

Burners cycle with the call on: filter, airflow, limit. Flame after the call ends: gas OFF, furnace out of service CALL JOSH

ALWAYS CALL JOSH FORGas valve · board · any motor · pressure switch · limit or rollout swap · any CO · cracked heat exchanger · same fault twice · any repair not on the price sheet
PART FAILED? ASK WHYBlocked flue kills inducers · dirty filter trips limits · water or a short kills boards · dirty rod or bad ground weakens flame
PROVE IT BEFORE YOU LEAVETwo full cycles, the second from cold · re-take the bad reading · CO at the flue and in the room · write the cause in HCP · clean up, then vacuum