STOP: gas smell, CO alarm or burnt wires. Everyone out. 911 and Xcel gas 800-895-2999 from outside, then CALL JOSH.
Faint gas smell at the furnace only: thermostat OFF, close its gas valve, no flames, CALL JOSH.
Faint gas smell at the furnace only: thermostat OFF, close its gas valve, no flames, CALL JOSH.
DIAGNOSIS CLOCK · 45 MIN
45:00
Start when you start diagnosing. A web page cannot alarm a locked phone, so set your phone timer too.
1Call for heat24V from W to C at the board○
2Board checks the safetiesBlink code. Limits and rollouts closed○
3Inducer starts120V at the inducer motor○
4Pressure switch closesWC on the manometer. 0V across the switch○
5Igniter glows orange120V at the igniter○
6Gas valve opens24V at MV and C. Meter on BEFORE the call○
Never touch the regulator, gas pressure, test ports or gas pipe.
7Flame lights and staysµA on the sensor wire○
8Blower starts120V at the blower after the delay○
9Call endsValve closes, blower runs on, then stops○
Flame still burning after the call ends or the valve should be closed: shut off the gas, take the furnace out of service, CALL JOSH.
Control board = LAST suspect. Only when 120V is in, 24V is in, the call is present, the safeties are closed, the pressure switch is proven, and there is still no output. Board replacement = CALL JOSH.
STUCK? Stumper guide
Everything tests good and it still won't run? That happens. Slow down and work it like this. Find the last step that worked. The problem is in the next one.
Stop now. No texting, no 45-minute clock: gas smell, CO alarm, scorched wires, flame out the front, or a tripped rollout. Furnace OFF. Gas or CO: everyone out, call 911 and Xcel gas 800-895-2999 from outside, then CALL JOSH.
A. Reset your head
B. Checks passed, still fails. Look here.
0 No power at all (board dark)
- Furnace switch off, door switch not pressed, breaker, blown board fuse.
- Blown fuse: find the short first (pinched thermostat wire, wire touching metal). Same-size fuse only. Blows twice = CALL JOSH.
1 Call for heat
- Jump R to W at the board (that is a call for heat, not a safety). Furnace starts = the thermostat or its wire is the problem.
- Loose or corroded W wire. Weak thermostat batteries.
2 Safeties (limits, rollouts)
- Reads closed cold, opens hot: check airflow first (filter, closed registers, blower). Then a loose spade on a switch.
- An open limit or rollout can stop the cycle before the inducer starts. Read the blink code.
- Rollout tripped: leave the furnace OFF and CALL JOSH. Don't reset it and run it. A blocked flue is one reason it trips.
- Limit or rollout replacement = CALL JOSH.
3 Inducer
- Won't start: 120V at its plug? 120V but no spin = the motor, CALL JOSH. No 120V = read the blink code, then check step 2.
- Starts, then quits: motor heating up, dirty or rubbing wheel, loose neutral.
4 Pressure switch
- Closes cold, drops out hot: water in the hose, cracked or pinched hose, blocked vent (nest, rust), inducer slowing down.
- The switch itself = CALL JOSH.
5 Igniter
- Glows but gas won't light: igniter dim or slow to glow, dirty burners, igniter out of position.
- Never glows: 120V at the igniter? None = back up the chain. Handle an igniter by its base, never the element.
6 Gas valve
- Look only: valve switch ON, shutoff handle in line with the pipe. Found it closed? CALL JOSH before you open it.
- 24V at the valve only lasts a few seconds. Meter on before the cycle starts.
- 24V there, igniter hot, no flame = CALL JOSH. No 24V = back up the chain (wires, ground, board).
7 Flame
- Lights, then drops in 3 to 5 seconds: dirty or oxidized rod, poor furnace ground, hot and neutral reversed, open neutral, cracked rod porcelain, flame not touching the rod.
- Clean the rod with a light abrasive pad and rerun. Low or bouncing flame signal = rod or ground.
8 Blower
- Won't start: give it 2 minutes (fan-on delay).
- Door switch not pressed. It is a safety: never tape or jumper it.
- Loose motor plug. PSC motor: weak run capacitor (power OFF, discharge it before you touch it). ECM: both plugs seated, power OFF.
- Motor or ECM module bad = CALL JOSH.
9 Runs, then shuts down
- Read the blink code first.
- Limit tripping: low airflow (filter, registers, blower slow or off). Pressure switch dropping out hot (step 4). Dirty flame rod (step 7).
- Thermostat satisfied early: thermostat location, loose thermostat wire.
C. Things that fool you
D. Still stuck? In this order
Part failed? Find out WHY
| Inducer motor | Partly blocked flue or vent. Check the vent, termination (nest, snow, frost), 90%+ trap, WC. Dirty or rubbing wheel. |
| Pressure switch | Cracked or wet hose, plugged ports, restricted vent |
| Limit or rollout | Dirty filter, closed registers, slow blower, blocked flue |
| Igniter | Age, cracks, touched with bare fingers |
| Flame sensor | Dirty rod, poor ground |
| Board | Water, rust, a rodent, a loose connector, a short |
| Blower or capacitor | Restricted filter or duct, heat, age |
| Gas valve, burners | CALL JOSH |
Parts do fail from age, but most of the time something made them fail. Don't swap and walk away. A flue that won't clear, or soot in the heat exchanger: CALL JOSH.
Meter rules
Prove it before you leave
Fixing one part can hide the real cause. Check twice, then write it down.
Write it down in HCP
Price talk: the only price you give is our hourly rate, $185 an hour. Never give a price from memory. For any other price, check the price sheet or call Josh.
Job done: tap this. A question or info any time: tap TEXT JOSH at the bottom. Both open a text to Josh with your steps, minutes and notes filled in. You still press Send.
For a single-stage, hot-surface-ignition furnace. Two-stage, variable-speed, 90%+, pilot or spark ignition add parts and switches: read the wiring diagram on the furnace door, then CALL JOSH before you go deeper. A yellow Ask Josh tag is a number Josh will give you.