No-Heat Diagnostic

Follow the sequence · gas furnace · Call Flow step 6 · Truck card

Saved
STOP: gas smell, CO alarm or burnt wires. Everyone out. 911 and Xcel gas 800-895-2999 from outside, then CALL JOSH.
Faint gas smell at the furnace only: thermostat OFF, close its gas valve, no flames, CALL JOSH.

DIAGNOSIS CLOCK · 45 MIN

45:00
Start when you start diagnosing. A web page cannot alarm a locked phone, so set your phone timer too.
START: step 1
1Call for heat24V from W to C at the board○
2Board checks the safetiesBlink code. Limits and rollouts closed○
3Inducer starts120V at the inducer motor○
4Pressure switch closesWC on the manometer. 0V across the switch○
5Igniter glows orange120V at the igniter○
6Gas valve opens24V at MV and C. Meter on BEFORE the call○
Never touch the regulator, gas pressure, test ports or gas pipe.
7Flame lights and staysµA on the sensor wire○
8Blower starts120V at the blower after the delay○
9Call endsValve closes, blower runs on, then stops○
Flame still burning after the call ends or the valve should be closed: shut off the gas, take the furnace out of service, CALL JOSH.
Control board = LAST suspect. Only when 120V is in, 24V is in, the call is present, the safeties are closed, the pressure switch is proven, and there is still no output. Board replacement = CALL JOSH.
STUCK? Stumper guide
Everything tests good and it still won't run? That happens. Slow down and work it like this. Find the last step that worked. The problem is in the next one.
Stop now. No texting, no 45-minute clock: gas smell, CO alarm, scorched wires, flame out the front, or a tripped rollout. Furnace OFF. Gas or CO: everyone out, call 911 and Xcel gas 800-895-2999 from outside, then CALL JOSH.
A. Reset your head
B. Checks passed, still fails. Look here.
0 No power at all (board dark)
1 Call for heat
2 Safeties (limits, rollouts)
3 Inducer
4 Pressure switch
5 Igniter
6 Gas valve
7 Flame
8 Blower
9 Runs, then shuts down
C. Things that fool you
D. Still stuck? In this order
Part failed? Find out WHY
Inducer motorPartly blocked flue or vent. Check the vent, termination (nest, snow, frost), 90%+ trap, WC. Dirty or rubbing wheel.
Pressure switchCracked or wet hose, plugged ports, restricted vent
Limit or rolloutDirty filter, closed registers, slow blower, blocked flue
IgniterAge, cracks, touched with bare fingers
Flame sensorDirty rod, poor ground
BoardWater, rust, a rodent, a loose connector, a short
Blower or capacitorRestricted filter or duct, heat, age
Gas valve, burnersCALL JOSH
Parts do fail from age, but most of the time something made them fail. Don't swap and walk away. A flue that won't clear, or soot in the heat exchanger: CALL JOSH.
Meter rules
Prove it before you leave
Fixing one part can hide the real cause. Check twice, then write it down.